Design standards

The numbers under a permit, not a guess from a catalog.

EPA writes manuals. New York writes Appendix 75-A. The county stamps the plan. Run Table 1 flow, Table 3 tanks, Table 2 setbacks, Table 4A perc, and the 75-A.8 / .9 siting tests. This is a briefing, not a stamped drawing.

House load

Codes size from bedrooms, not from how many people slept there last Tuesday. An expansion attic counts.

Bedrooms

3

Design flow · Table 1

What Table 3 says

Appendix 75-A Table 1. New construction with 1.6 gpf toilets sizes at 110 gpd per bedroom.

Design flow
330 gpd
Table 3 equivalent bedrooms
3
Minimum tank
1,000 gal
Minimum liquid surface
27 ft²
Two × daily flow (other codes)
1,000 gal

NY uses the bedroom table, not two-times-flow, and floors at 1,000 gallons for 1–3 bedrooms. Two compartments, an outlet baffle, and a listed effluent filter are construction notes, not extras.

NY Appendix 75-A Table 3 minimum septic tank capacities
BedroomsGallonsLiquid surface
1–31,00027 ft²
41,25034 ft²
51,50040 ft²
61,75047 ft²
Each extra+250+7 ft²

Tank gallons and liquid surface follow NY Appendix 75-A Table 3. Design flow follows Table 1 (110 / 130 / 150 gpd per bedroom). Perc rates follow Table 4A. Setbacks follow Table 2. Raised and mound siting follow 75-A.9. County health departments may be stricter. Not a permit.